G9SA-301 AC100-240產(chǎn)品概述
G9SA-301 Dual-Channel: Power Requirements: The G9SA-301 will accept 24 VAC/VDC or 100 to 230 VAC. Inputs: The G9SA-301 will accept single or dual NC inputs or dual inputs from a light curtain (see G9SA-301 for application wiring for a light curtain). Outputs: The G9SA-301 has 3 NO outputs to route power to the coils of power contacts, plus 1 NC auxiliary output for signaling purposes. External Device Monitoring (EDM) is provided with a Feedback loop between T31 and T32 on the G9SA-301. Reset Mode: Automatic or manual reset modes are available on the G9SA-301.